I went on an inspection right after another electrical company had completed a surge protection install.
The surge protector is mounted in the wall below panel.
Can you spot the problem we have here?
1. There wasn’t enough resistance to ground, only one ground rod installed.
2. They pigtailed the surge protector to the dryer circuit with the taps very loose(so loose that when I removed the wire nuts the wires fell apart) this would cause the taps/joint to heat up causing a fire.
3. Surge protection should always be closest to the load side of the main breaker when installing in this location.
Be careful who you choose to protect your investment.