03/12/2026
CITY OF NEWPORT BEACH COMMUNITY DEVELOPMENT DEPARTMENT | BUILDING DIVISION
100 Civic Center Drive | P.O. Box 1768 | Newport Beach, CA 92658-1768 | www.newportbeachca.gov | (949) 644-3200 ________________________________________________________
Updated: January 8, 2026
EXPRESS OnlinE REROOf PERmitEXPRESS ONLINE PERMITS:
A reroof permit is available through the City’s Civic Portal at:
www.newportbeachca.gov/online permitting
The following conditions must be met:
1. The structure is one- or two-
family residential dwelling.
2. The new roofing weight is 6 lbs/ft
or less in weight.
3. Only one existing layer may be
recovered.
If any of these conditions are not met, the express permit cannot be obtained and must be submit for review.
Minimum Roofing Requirements
INSPECTION REQUESTS CRITERIA:*
Tear-Off / Sheathing Inspection
1. Materials shall be removed & the roof sheathing exposed.
2. Verify structure is adequate for roofing system loads.
3. If sheathing is required, it must be completed prior to inspection. 4. All materials must be available for inspection: underlayment, nails,
flashing, and attachments.
5. Existing flashing may be reused if in good condition.
6. Provide ladder 3 feet higher than landing on roof and tied-off.
Final Inspection
1. All work is complete, and the spark arrester(s) are installed.
2. Roof and job site clean of debris.
3. Gutters must be reinstalled (if removed) at time of inspection.
4. Ladder must be installed and tied-off.
5. Carbon Monoxide / Smoke Alarms are to be installed (self-certification
form is acceptable).Flashing: Felt: Roofing: Eave Vents: Attic Vents:
26-gauge galvanized steel or 0.019” 30 lb. felt underlayment
Listed Class B or greater
Permitted
Openings shall be minimum 1/8 inch and shall not exceed 1/4 inch*Minimum Roofing Requirements for properties subject to Wildfire Exposure – (CWUIC 504) (See attached Fire Hazard Severity Zone Map for High and Very High zones)Flashing: Felt: Roofing: Attic Vents:
Gutters:
26-gauge galvanized steel or 0.019”
72-pound mineral-surfaced, non-perforated cap sheet complying with ASTM D3909
Listed Class A per ASTM E108 or UL790
Ember resistant vents per CWUIC 504.10 approved and listed by the California State Fire Marshal, or WUI vents tested to ASTM E2886 and listed. Openings shall be minimum 1/16 inch and shall not exceed 1/8 inch
Roof gutters shall be noncombustible and screened to prevent accumulation of leaves and debris (CWUIC 504.4)