Bassett Sprinkler Protection

Bassett Sprinkler Protection Educating people about how sprinkler systems work, save lives, money and reduce fire & water damage

If you've been written up for a 5 year internal inspection and are wondering why would they need to do that. Here is you...
01/24/2026

If you've been written up for a 5 year internal inspection and are wondering why would they need to do that. Here is your answer, One picture. This is on a dry system thats poorly maintained. This is the actual supply main. There was 3 or 4 branchlines effected by this sediment.

Alittle while back a customer hired us to fix a fire main leak.where we were digging was a alley way between 4  building...
01/24/2026

Alittle while back a customer hired us to fix a fire main leak.where we were digging was a alley way between 4 buildings. There was a ton of mechanicals running through the excavation site. We located the leaks and found the piping to be in poor shape. We ended up replacing 100% of the bad piping. The customer had bad experiences with previous contractors having their new work blowing apart. So they required us to not only pour our thrust blocks, but to rod and anchor every joint. This job was a ton of work and a ton of fighting to get it completed. We even added a couple wall hydrants that the customer wanted

Here is a Fire pump where we pulled the rotating assembly. We checked the shaft and replaced the bearings.After we check...
01/24/2026

Here is a Fire pump where we pulled the rotating assembly. We checked the shaft and replaced the bearings.After we checked the alignment of the driver. Then to wrap it up we cleaned the body and lid of the pump repacked it and replaced the head gasket. This pump is back in service and ready for hopefully another 20 years of service

This is a great example of just because they say they can, doesn't mean they actually  can
01/24/2026

This is a great example of just because they say they can, doesn't mean they actually can

01/24/2026

This was a unfortunate day for our guys, this was the main drain on a floor for a property we were hired to relocate some sprinkler heads at. As you can see the sink didn't take the demand for water during a very painfully slow draining process. Now imagine this drain is supposed to run wide open once a year during the inspection.

01/24/2026

Here is a warehouse we just wrapped up.3- 30,000 sq foot + ESFR systems in total tested, inspected and approved all within a month and a half. From delivery of pipe and material up until the last hydro it took our guys a little more then a month

Have you ever seen an on/off sprinkler?
12/08/2025

Have you ever seen an on/off sprinkler?

07/02/2025
05/17/2025
A brand new building we recently sprinklered, had a fire. Shout out to Reliable Automatic Sprinkler Co., Inc. 2 of their...
05/16/2025

A brand new building we recently sprinklered, had a fire. Shout out to Reliable Automatic Sprinkler Co., Inc. 2 of their F1FR80 uprights managed to contain a lithium-ion battery fire.

It was a beautiful day for a flow test. 59 Pitot out of a 2-1/2" outlet.
04/25/2025

It was a beautiful day for a flow test. 59 Pitot out of a 2-1/2" outlet.

Friday we were out on an emergency underground repair. Thwre was an 8 foot long crack with a ½" of separation right on t...
04/05/2025

Friday we were out on an emergency underground repair. Thwre was an 8 foot long crack with a ½" of separation right on the bottom of an 8" ductile main. With 100 plus psi, this made a major mess. Quick response time, and the knowledge of shutting the main down, enabled us to minimize the mess. From start to finish this was a 1 day repair. We cut out the damaged section and replaced it with new pipe and fittings. Our customer is back in service and no longer on fire watch

Address

4250 W 130th Street
Cleveland, OH
44135

Opening Hours

Monday 8am - 5pm
Tuesday 8am - 5pm
Wednesday 8am - 5pm
Thursday 8am - 5pm
Friday 8am - 5pm

Telephone

+12164762500

Alerts

Be the first to know and let us send you an email when Bassett Sprinkler Protection posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Contact The Business

Send a message to Bassett Sprinkler Protection:

Share