31/07/2026
Sharing My Troubleshooting on Ballast Remote Valve No. 14, 15, and 16 Not Responding After Command‼️
The Chief Officer reported that Ballast Remote Valves No. 14, 15, and 16 were not responding to remote open and close commands from the Ballast Control System. Upon receiving the report, an initial inspection was carried out through the Alarm Monitoring System (AMS) to verify the communication status of the affected remote valve system. No communication fault or loss of communication was indicated by the AMS, suggesting that the PLC communication network was functioning normally.
To further investigate the issue, an onboard inspection was conducted at the solenoid valve cabinet located in the pipe tunnel. The electrical wiring diagram was reviewed, and it was confirmed that the PLC communication circuit and the 24 VDC power supply for the solenoid valves are supplied by separate power sources. During inspection, the dedicated 24 VDC power supply feeding the solenoid valves was found to be defective, resulting in the affected solenoid valves receiving no operating voltage. This explains why the AMS did not register any communication failure, as the PLC communication power supply remained operational while only the solenoid valve power supply had failed.
As part of the troubleshooting process, the resistance of all connected solenoid valve coils was measured and compared. All solenoid valves were found to have good and nearly identical resistance values, indicating that the coils were in good condition. Additionally, insulation and continuity checks confirmed that no short circuit was present in the solenoid valve wiring or load circuit. These findings eliminated the solenoid valves and field wiring as the source of the fault and confirmed that the problem originated from the power supply unit.
The power supply unit was removed and tested separately in the workshop, where it initially produced a normal 24 VDC output under no-load conditions. However, once reinstalled and connected to the actual system load, the power supply immediately shut down and was unable to maintain its 24 VDC output. This behavior indicates that the power supply is unable to deliver the required current under load. The most probable cause is an internal failure of the power supply, such as degraded electronic components or a faulty overload/protection circuit, causing the unit to trip and shut down whenever a load is applied. Since the connected solenoid valves and wiring were verified to be in good condition and free from short circuits, the failure is most likely internal to the power supply itself.
At present, a replacement 24 VDC power supply has been requested and is awaiting delivery. As a temporary operational measure, Ballast Remote Valves No. 14, 15, and 16 are being operated manually whenever ballast operations require them to be opened or closed, ensuring that ballast operations can continue safely until the defective power supply is replaced.