04/06/2026
I was at an interesting one today. For context, I was at a property to service two boilers, a 30KW and a 29KW.
I went straight to the meter and noticed they had the outlet in 22mm, to supply 59KW 🤦♂️ if both boilers were very close to the meter you’d maybe get away with it.
For engineers out there the photographs are as follows;
1st OP at meter
2nd OP at farther away boiler
3rd OP at farther away boiler with second boiler in operation
Needless to say a call to gas safe was needed as I was panicking I would have to shut them down until gas line had been upgraded. Now, according to gas safe;
The line as it stands, as long as FGA and gas rate at each boiler is ok, is classed as NCS. I thought AR at minimum but I was wrong! Enables me to make the customer aware and book in to come back and upgrade the gas line.
No matter how long you have been in this game there is always more to learn! Thought I’d share this incase any other engineer runs into a similar circumstance.
This is why I always go on about doing gas line calculations properly, it really burns my custard when I see this kind of thing 🤦♂️