Ohayou gozaimasu! ๐Ÿค—Situation:Forward Port Side Bilge Well HAL (High Alarm Level) Sensor not working! ๐Ÿ˜…Preliminary Action...
27/05/2026

Ohayou gozaimasu! ๐Ÿค—

Situation:

Forward Port Side Bilge Well HAL (High Alarm Level) Sensor not working! ๐Ÿ˜…

Preliminary Action:
-Checked AMS (Alarm Monitoring System) baka naka simulte to Off pero hindi naman or baka sobrang tagal ng delay para mag alarm pero hindi din naman.
-Punta sa mismong location ng Bilge Sensor
(Ang sikip wala pang hagdan pababa sa location. Chikushou! No good design pangyao ah! ๐Ÿ˜…)
-Linis ng stem ng sensor then up and down yung float pero no alarm pa din

Main Troubleshooting:
Ikemasu! ๐Ÿƒโ€โ™‚๏ธโ€โžก๏ธ
-Inilabas ko na ang pangmalakasang Fluke Multimeter (Fluke baka naman? ๐Ÿ˜‚)at binuksan ang cover ng sesnsor to gain access sa terminals at tinester ang lines. Kapag nakalow level 0 volts pero pag naka high 8.9 volts lang .
-Dinisconnect ko ang mga cables and tested ang resistance ng sensor. Kapag High Level nasa 398 kilo Ohms at kapag Low Level ibig sabihin ok pa ang sensor.
-Tested the Cables going in the sensor 8.9 volts lang. Hmmm... around 24 Volts dapat to ah. ๐Ÿค”
-Akyat sa Alarm Monitoring System at chineck saan naka connect ang Forward Port Side Bilge Well HAL. At ayon dun connected siya sa PLC 3 > BIM2200 na Card. PLC 3 in this case ay yung SAU 03. Nasa isang Electrical Cabinet siya sa Engine Room Named Signal Acquisition Unit 03. Lyngso Marine nga pala ang AMS (Alarm Monitoring System) namin.
-Pinuntahan ko na ang SAU 03 Cabinet and located the terminals for the Forward Port Side Bilge Well at pagka disconnect ko ng cables nag alarm agad. Pumunta din muna ako sa AMS para i-simulate to off ang status ng sensor para hindi alarm ng alarm.
-I tested this BIM2200 Terminals (Sugoi English! ๐Ÿ˜ฎ) at may 24V itong output so ibig sabihin somewhere pababa sa sensor ay maaring may grounding or putol kaya nababawasan ang voltage papunta sensor
-Sa malapit ako sa sensor nag umpisa at nandun ko nakita malapit sa sensor na may connection covered ng shrinkable tube at pag open ko the connection was cut, wet, and grounded.
-Pinutol ko yung connection at dahil mahaba pa ang cables directly ko na siya ikinonect sa sensor
-Naglagay din ako ng silicon for additional water ingress protection.
-Ibinalik ko sa Normal ang settings sa AMS then baba uli and tested at okay na.
-Pagkatapos nun sinecure ko na lahat pati puso mo (Yamete Senpai! ๐Ÿ˜‚) Linis ng mga kalat. Yung mga pinagputulang cable, tapes, at inalis na shinkable tubes dapat hindi sila mapunta sa Bilge Well.

Yun lang medyo napahaba.

Sugoi deshou? ๐Ÿคทโ€โ™‚๏ธ
Kimochi na naman si Senpai! โ˜บ๏ธ
Ja Mata ash*ta ne! ๐Ÿค—
Kiotsukete ne mga kouhai at senpais! ๐Ÿ™‹โ€โ™‚๏ธ

Hisashiburi, mina-san! ๐Ÿค—Ohayou gozaimasu! ๐Ÿ˜ƒSituation:Prangko na tapos natawagan tayo ni 2/E Ukranian.Hindi niya daw mapa...
24/05/2026

Hisashiburi, mina-san! ๐Ÿค—
Ohayou gozaimasu! ๐Ÿ˜ƒ

Situation:

Prangko na tapos natawagan tayo ni 2/E Ukranian.
Hindi niya daw mapaandar ang probision compressor.
May alarms pero hindi niya alam kung ano.
Kakasampa lang namin sa barkong ito at pa 6th day pa lang namin.

Troubleshooting:

Tiningnan ko ang panel at ayon sa alarm from the HMI (Human Machine Interface) Panel "Discharge Pressure Too High Alarm"

Bago ito mangyari mababa ang pessure ng LT Cooling kasi nag rerepair sila ng pipe kaya natrigger talaga ang high discharge pressure switch. 2 hours ago pa yun nangyari. Sa ibang pressure switch may reset para maalis ang pagka cut out niya due to high pressure. Itong naka install sa amin ay wala. At looks like may naiwan pa talagang high pressure sa linyada papuntang pressure switch.

Solution:

Pinihit ko clockwise ang screw ng cut out para mawala ang pagka cut-out ng pressure switch. Pag andar ng provision compressor the dischage pressure was normal at ibinalik ko na sa dating cut-out setting sa pagpihit ng screw counter clockwise.

P.S.:

Napatanong si 2/E what to do daw next time and I told him what I did. Napa thank you my friend siya sabay tanong what is my name. First time kasi namin magkasama. Pagkasagot ko tinanong ko na din tuloy siya sabay sabing you're welcome!

Sugoi deshou? ๐Ÿคทโ€โ™‚๏ธ
Kimochi na naman si Senpai! โ˜บ๏ธ
Ja Mata ash*ta ne! ๐Ÿค—
Kiotsukete ne mga kouhai at senpais! ๐Ÿ™‹โ€โ™‚๏ธ

Hisashiburi, mina-san! ๐Ÿค—Ohayou gozaimasu! ๐Ÿ˜ƒSituation:One hour notice for arrival sa Harwich, U.K., tinawagan tayo ni 3rd...
23/01/2026

Hisashiburi, mina-san! ๐Ÿค—
Ohayou gozaimasu! ๐Ÿ˜ƒ

Situation:

One hour notice for arrival sa Harwich, U.K., tinawagan tayo ni 3rd Engineer. Hindi daw niya ma-excite ang Shaft Generator No. 2. Okay punta ako jan.
Shimatta! Pag si 3/E ang natawag medyo mabigat lagi ang trouble ah! ๐Ÿ˜‚

Standard Operating Procedure:

Kapag parating ang barko o paalis sa isang port, One Hour Notice given to everyone para sa pagbitaw o pagdikit niya sa isang puerto.
May mga Navigational Equipments at Deck Machineries na mga Navigators/Deck Department ang namamahala.
May mga machineries na need paandarin at ipara na ang Engineers/Engine Department ang namamahala.
At lahat halos ng gamit nila gumagamit ng Electricity kaya kailangan tayong mga Electrician/ETR/ETO to be on always on standby and be called to maintain and to repair if problem arises on its electrical parts, mainly its controls.

Main SOP:

Meron kaming 2 Shaft Generators at 2 Main Generators onboard.
Meron din kaming 2 Bow Thrusters.
Situational kung alin ang nakaservice na Shaft Generator at gagawing in service na Main Generator.

For Arrival ito ang SOP:
1. Run Main Diesel Generators No. 1 & 2.
2. Shift all of the ship's electrical load from Shaft Generator No. 2, which is currently in-service, to the Main Generators No. 1 & 2.
3. Disconnect Shaft Generator No. 2 from the Main Switch Board.
4. Excite Shaft Generator No. 1 and Connect Forward Bow Thruster to Shaft Generator No. 1 as its Main Consumer.
5. Connect Aft Bow Thruster to to Shaft Generator No. 2 as its Main Consumer.

Note: Lahat ito ay ginagawa ng pa click click lang through the computer we commonly call Alarm & Monitoring System.
Kongsberg yung meron namin dito onboard.

Pagdating sa Engine Room:
Ang Duty Engineer this time is 3/E.

Troubleshooting:

Ikemasu! ๐Ÿƒโ€โ™‚๏ธโ€โžก๏ธ
Primary step ng troubleshooting is ask the operator ano yung sinusunod niyang procedure at paano niya paandarin ang machineries.
Ang tawag niya ay hindi ma-excite.
Na-eexcite naman pala pero kulang yung voltage para mag proceed to take loads.
Imbes na 400 V AC the Bus Voltage created by Shaft Generator No. 2 is only 301 to 302 Volts AC.
Nagpunta tayo sa Main Switch Board (MSB) on the Shaft Generator No. 2's Panel.
Nag browse tayo ng parameters sa Protection and Paralleling Unit (PPU) at totoo ang reading sa AMS na 301 to 302 Volts lang ang na-ke-create na voltage ng SG No.2.
Dahil di niya ma-excite from the computer ang reklamo sabi natin na de-excite niya muna at nakarating kay AVR via this panel ang De-Excite command dahil maririnig mong may nag click.
Next sabi natin i-excite niya at nakarinig uli tayo ng click at tumaas na uli ang Voltage to 301 - 302 Volts AC.

2 suspects agad ang nasa isip natin.
It is probably the AVR or the Rotating Diodes.
Depende sa design, merong AVR na nandito sa likod ng panel nakalagay at meron ding malapit sa body ng Generator nakalagay.
Itong time na ito nakalagay siya sa body ng Shaft Generator No. 2.
Ayaw muna ipagalaw ni Chief Engineer dahil padikit nga.
Bumaba na ako sa location ng Shaft Generator to investigate the location ng AVR, at ano mga need para ma-access.
The Shaft Generator No. 2 Alternator is an AvK DSG 86 K1-4.

For the rotating diodes, alam ko na situated siya sa dulong part ng alternator dahil nagpapalit ako ng air filter kasabay ang inspection ng alternator windings on this side at may new spares kami nito from our AMOS inventory.

Pagkapara ng M/E nung makadikit na at secured na ang lahat, we opened the alternator covers from the end side where i replace air filters. Pagkatapos binuksan namin ang cover sa aft side ng Alternator.
Dinischarge natin ang mga terminals by shorting it to the body ng Alternator.
Tinest din natin kung may voltage pa sa mga windings before proceeding.
I then disconnected the cables from the Rotating Diodes.
Maganda yung design dito dahil by screw lang yung connections ng Rotating Diodes.
Wala ka kailangan i-desolder at i-solder.
Tinest natin ang mga Rotating Diodes at we found out that some on Reverse Bias ay may mga Readings na sa Ohm Meter settings ng Multitester natin.
Ang mga bagong Rotating Diodes show O.L. (Open Loop) sa Multitester natin.
Fluke baka naman? ๐Ÿ˜‚
Yamete Senpai! ๐Ÿคซ

Paano mag-test ng Diodes?
Tinuturo naman ito sa schools, pero magkakaiba din kasi ang mga Diodes.
Itong Rotating Diodes namin madali malaman ang anodes and cathodes.
Refer on the attached pic na lang mga kouhais.

Pinalitan natin all Diodes ng new spares.
Dalawa lang sana papalitan ko pero sabi ni Chief Engineer "Better change all because all of them were already running for very long time".
Sugoi English! ๐Ÿ˜ฎ Swedish si Chief Engineer e. ๐Ÿ˜…
Sa mga ibang lahi nakasama ko dati, "Palitan mo na lahat! Mayaman ang kumpanya natin!" ๐Ÿ˜‚

We ran Main Engine No. 2,
Clutched-In to make the alternator rotate,
and tried to excite SG No. 2 kaso same trouble pa din.
One Hour Notice na din for Departure naman so we stopped muna and consult with manual and some senpais.

Kinabukasan pagdating ng port of Rotterdam, Netherlands, pinaalam natin yung next step natin kay C/E.
Meron kasing External Voltage Potentiometer sa likod ng SG No. 2 Panel sa May MSB at hindi fixed ang resistance nito.
It is varying constantly.
Kaya sinabi natin sa kanya na i-reremove natin ito.
According to manual need ding i-short ang S and T terminals kung saan mo ididisconnect to.

Ang AVR ni SG No.2 ay Cosimat N+ at tinest po agad natin ang fuses niya pagkabukas natin ng covers. Okay naman sila.
Sa R4 tayo nagbawas ng Voltage. Isang full na ikot counter clock wise din.
Please refer uli sa attached photos mga senpais and kouhais.

We ran Main Engine No. 2,
Clutched-In to make the alternator rotate,
and meron na agad 77V AC na Bus Voltage si SG No. 2.
Pagka-excite namin naging 420V ang Bus Voltage niya at ready na din siya to take loads.
I went to the AVR at adjusted down to 401V AC.
400V AC kasi ang working Voltage namin dito sa barko.

Nag secure muna kami at pagdating ng departure niloadan na namin siya ng Bow Thruster at there was no significant voltage decrease.
Nung nasa maluwag na kami tinest namin ibigay lahat ng electrical load sa SG No. 2 at there was also no significant voltage decrease.

Last Part ng uploads ay video ng pag take ng SG No. 2 ng all electrical loads.

Sugoi deshou? ๐Ÿคทโ€โ™‚๏ธ
Kimochi na naman si Senpai! โ˜บ๏ธ
Ja Mata ash*ta ne! ๐Ÿค—
Kiotsukete ne mga kouhai at senpais! ๐Ÿ™‹โ€โ™‚๏ธ

22/01/2026

Di ko alam kung malas o swerte pero twice ko naexperience yan sa dalawang magkaibang container vessel na nasakyan ko.
Matagal na trabaho yan lalo pag ang wiring e nabago na at wala na mga taggings.
Omedeto gozaimasu senpai-sama! ๐Ÿ˜…

With Elmismo Vlogs โ€“ I just got recognized as one of their top fans! ๐ŸŽ‰
20/01/2026

With Elmismo Vlogs โ€“ I just got recognized as one of their top fans! ๐ŸŽ‰

I've just reached 100 followers!Domo arigatou gozaimazu for the support my kouhai's and senpai's!I could never have made...
16/01/2026

I've just reached 100 followers!
Domo arigatou gozaimazu for the support my kouhai's and senpai's!
I could never have made it without each one of you.
Ikuzo! ๐Ÿ™๐Ÿค—๐ŸŽ‰

With DiskartengMarino โ€“ I just got recognized as one of their top fans! ๐ŸŽ‰Arigato Gozaimasu Senpai! :D
13/01/2026

With DiskartengMarino โ€“ I just got recognized as one of their top fans! ๐ŸŽ‰

Arigato Gozaimasu Senpai! :D

Ohayou minna-san! ๐Ÿค—Shimatta! Bagong taon bagong alarm na naman! ๐Ÿ˜‚Situation:ES1-1 WIRE BREAK Alarm.Around new year's time...
13/01/2026

Ohayou minna-san! ๐Ÿค—

Shimatta! Bagong taon bagong alarm na naman! ๐Ÿ˜‚

Situation:

ES1-1 WIRE BREAK Alarm.

Around new year's time, tumawag si 3E at ito daw ang alarm.

Preparatory for Troubleshooting:

Upon checking sa Electrical Diagrams, ang ES1 ay Emergency Stop Button to stop lahat ng Oil Pumps sa Engine Room.
At upon checking more on the Electrical Diagrams, si ES1-1 ay located sa Wheel House mas kilala natin as Bridge.
Chikushou!
Hindi pwedeng gawin habang tumatakbo ang barko. ๐Ÿ˜…

Troubleshooting No.1:

Ikemasu! ๐Ÿƒโ€โ™‚๏ธโ€โžก๏ธ
Chineck ko muna yung ES1-1 Button sa Bridge.
Kako baka maluwag lang yung EOL Resistor dahil ng higpitan ko nawala yung Alarm pero after 2 hours nanjan na uli siya.

Since darating ang Sabado kung saan kami ay maglelay-over pinaalam natin kay CE na itetest namin yung ES1-1 Button from Bridge on FWE Condition and with the Engineers present to reset the Shunt Tripped Circuit Breakers agad-agad to never cause black-out.
Dumating ang sabado at ginawa namin ito in actual at it triggered the shunt trips of all Oil Pumps in the Engine Room.
This confirms that there is no actual line break.
Kailangan dun naman sa pinuntahan ng ES1-1 Line na to ako pumunta.
Kaso nasaan siya?
Ang barkong nasakyan ko ay isang RO-RO Cargo Ship na nasa Forward Part ang Bridge at nasa Aft Part ang Engine Room.
The Diagram Says na nasa Emergency Switch Board itong connection pero pagpunta ko dun wala naman siya sa Emergency Generator Room where the ESB can be found.

Understanding the Electrical Diagram:

Sa mga conventional Electrical Diagrams, Emergency Stops are wired only with Normally Closed Push Buttons na pag pinindot nyo ay maka cut ang daloy ng electricity and you will never be able to run the circuit again unless i-reset mo ang Emergency Stop.

For safety reasons, iba ang wiring nito.
Ito yung madadaanan nyong topic nung nag-aaral pa lang tayo sa engineering na Protective Relaying.
Pero sa totoo lang wala talaga ako maalala dun sa topic na yun kundi yung topic lang.

Yamete kudasai! ๐Ÿ˜‚

It is wired with a Normally open push button, locking type, paralleled with an End-of-Line Resistor.
Itong line na ito ay minomonitor ng isang relay na kung tawagin ay overvoltage or undervoltage relay.
Kapag nagbago ang status ng mga contacts ni overvoltage or undervoltage relay which is monitored by a Programable Logic Unit na may Discrete Input Circuit na ang output ay going to another PLC na may Discrete Output Circuit, itong si PLC na may DOC ang mag papailaw sa ES1-1 WIRE BREAK Alarm at magbabato sa Alarm Monitoring System sa ECR na may EMERGENCY STOP BREAKER ALARM at MSB COMMON FAILURE Alarm at magpapatrip sa mga Shunt Trip Releases ng CB ng mga Oil Pumps sa Engine Room.

Normally, kapag pinindot mo ang ES1-1 Button, doon lang siya dapat aalarma, pero sa pagkakataong ito ay hindi.
At umaalarma siya na hindi naman niya ipinapara ang mga Oil Pumps.

Upon delving more sa Electrical Diagrams, may relay for the Alarms, which is K217.2-A, at may iba pang Relay, which is K217.2, for Tripping The Shunt Releases to the CBs ng mga Oil Pumps.
Medyo maliwanag na si K217.2-A ang salarin.

Troubleshooting No. 2

Ikemasu! ๐Ÿƒโ€โ™‚๏ธโ€โžก๏ธ
Sa kakabukas ng lahat ng Panel, nahanap natin ang mga PLC na sinabi ko sa Main Switch Board Synchronization Panel.
At sa ilalim nito, which sa mga nasakyan ko na before na barko ay either blank or Bus Bars ang nakalagay, doon ko nakita ang lahat ng Alarm Relays connected in parallel.
Kapag may malaking load na gumagana maririnig mong biglang magkiclick si K217.2-A at aalarma na si ES1-1 WIRE BREAK.
Inadjust natin si Hysteresis Loop pataas dahil this will make the relay less sensitive to fluctuations pero kahit sinagad natin ay hindi umubra.

Chikushou! ๐Ÿ˜‚

The Relay with problem is a Telemecanique RM4UA and it is not available onboard.
May mga katabi siyang Relays for alarms na napalitan na ng bagong model which is Schneider RM22UA22MR.
We checked the Data Sheet and it is a compatible replacement pala talaga.
I then checked the Inventory sa AMOS, which is our Electronic Preventive Maintenance System, at nakita ko na meron pa kaming 2 pieces nito.
At swerte naman meron nga spare physically. ๐Ÿ˜‚

Double checked all connections at "yabai" talaga. ๐Ÿ˜ฑ
If I will replace the problematic relay ay it will trigger all Wire Break Alarms, at kung sakaling maluwag ang connection niya kay K217.2, it could possibly send a signal to trip Oil Pumps.
So, ininform uli natin si CE at 2E na this coming Saturday, sa short lay-over namin ko titirahin.

Another Saturday came.
On Finished With Engine Condition, after nila magbunkering from first tanker barge, ini-adjust ko ang settings ng spare relay at ipinalit ko sa faulty relay.
It triggered all Wire Break Alarms, and Emergency Power Source Fail Alarm.
Luckily, The Emergency Power Source Fail Alarm was only an alarm at it did not trigger anything, except for another alarm in the AMS, pero the engineers are on alert naman if anything goes differently.๐Ÿ˜Œ

Pagkatapos palitan, the alarm never came back!

Sugoi deshou? ๐Ÿคทโ€โ™‚๏ธ
Kimochi na naman si Senpai! โ˜บ๏ธ
Ja Mata ash*ta ne! ๐Ÿค—
Kiotsukete ne mga kouhai at senpais! ๐Ÿ™‹โ€โ™‚๏ธ

Min'na Ohayou!Situation:Tumawag si Bosun at pumapara daw ang Center Mooring Winch sa Forward Mooring Area kapag nasa 2nd...
07/01/2026

Min'na Ohayou!

Situation:
Tumawag si Bosun at pumapara daw ang Center Mooring Winch sa Forward Mooring Area kapag nasa 2nd speed na.

Troubleshooting done:
Ikemasu!
Dahil prangko sila ng after lunch, mag-isa muna nating tinira yung trabaho.
Inireset ko muna ang Emergency Stop Button.
Operated it at tumitigil nga sa 2nd Speed.
Pinuntahan natin ang Panel at dahil ang panel dito has a main Power Switch na kailangang i-off para mabuksan ang panel ay ini-off muna natin ang Power Switch.
Pagkabukas ng panel, I switched ON the Power Switch.
Test muna ulit baka nakuha sa Reset pero ganun pa din.
Upon checking the Electrical Wiring Diagram, I found out K2 is the Contactor for 2nd Speed.
Gumamit tayo ng multimeter.
Fluke baka naman? ๐Ÿ˜…
Ok naman ang contacts baka kasi may naghinang.
Inamoy-amoy din natin baka amoy sunog pero wala namang amoy.
Sa Visual Inspection naman napansin natin na naka-angat ng bahagya sa body ng Contactor yang Auxiliary Contact na naka-oblong sa picture.
Natanggal pala siya, e yan ang holding contact ni K2 kaya pala pumapara sa 2nd Speed.
After maibalik, testing uli heave and slack all speeds working na.
Turn Off uli tayo ng Power Switch para masara ang Panel niya then pagka Turn On, Final Testing and working pa din siya.
So ayun ininform na natin si Bosun.

Kimochi di ba? โ˜บ๏ธ

Mata ne! ๐Ÿค—