This system is a couple years old and has given trouble along the way, this is the first time they’ve called ELITE! Pump burnt out by solids getting into the effluent tank. Pumped and washed down the entire system, pumps had to be pulled and cleaned and one replaced, identified the problem, the outlet baffle was a long sweep wye so the top of the outlet was about 4-5” lower than the outlet pipe allowing solids to flow straight out of solids tank. Made us up some “arm extenders” to reach the fitting about 10-12 feet down and extended the outlet up and also down to only allow effluent (cleanest) water in the tank to exit. Snaked a drain inside while we were there as well.