29/08/2022
How to calculate the value of Current Transformer transformers mounted on both sides of the transformer
*Transformer 80MVA
1- Current current value from the side of 110KV
Power (S) = 1.73 x V x I
I = 80000/(1.73 x 110)
I = 420 A
Of course there is no current transformer ratio of 420 so the largest value is used and we choose a current transformer of 500
2- Current current value from the side of 20KV
I = 80000/ (1.73 x 20)
I = 2313 A
And the same thing there is no current transformer in this ratio so the largest value is used and we choose a current transformer 2500
Note when choosing the value of the power adapter is according to the available percentages of the power transformers produced by companies
*There is no problem in choosing a higher current adapter ratio for example a transformer. Stream 1500 and there is no of it in the manufacturers or stores of the company A current transformer is installed at a higher rate of 1600 and there is no important problem not less than the current value calculated from the equation.
* Most companies resort to the production of multi-ratio transformers, for example, when changing the transformer from 25MVA to 40MVA, we need a transformer with a higher ratio, so the transformer is not changed as it used to happen previously
But the ratio of the current transformer from both ends of the primary or secondary coil is changed
The third current transformer on the neutral breakeven point is specific to REF restricted ground leakage and its value is the same value on the one hand.
The 110KV
Choosing the correct ratios of current transformers on both sides of the transformer is an important thing and we make sure of the correct ratios when making Diff Relay differential protection calculations and also when balancing the transformer Stability Test.